Standard Features
|
|
![]() |
|
DescriptionThe Micron 4-20 mA output, DC input transmitter provides six voltage input ranges and four current input ranges, all factory calibrated and jumper selectable. The 200.00 mV and 2.0000 V ranges provide a high input impedance of 1 Gohm to minimize the load on the voltage signal. A 5.000A range measures the IR drop across a built-in 10 mW current shunt. The transmitters can also easily be scaled in software for use with external shunts. Three analog transmitter settings are jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy. The output tracks the reading from -99,999 to +99,999 counts that would be transmitted digitally. For DC signals, this reading has a rated accuracy of ±0.01% of full scale input and can be scaled in software. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance. Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control. Standard features of Micron transmitters include:
Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04). |
Analog Input |
Range |
Resolution |
Input Ohms |
DC Voltage |
200.00 mV |
10 µV |
1 Gohm |
DC Current |
2.0000 mA |
0.1 µA |
100 ohms |
Input Resolution Input Accuracy Update Rate, Max Max applied voltage Over-current protection |
16 bits (65,536 steps) ±0.01% of full scale ± 2 counts 50/sec at 50 Hz, 60/sec at 60 Hz 600 Vac for 20, 200 & 600 V ranges, 125 Vac other ranges 25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, 1x for 5 A |
||
Analog Output (standard) |
|||
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Isolation |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load or higher) 16 bits (65,536 steps) 0.02% of output span plus conversion accuracy 250V rms working, 2.3 kV rms per 1 minute test |
||
Dual Relay Output (standard) |
|||
Relay Type Load rating |
Two solid state relays, SPST, normally open, Form A 130 mA at 140 Vac or 180 Vdc |
||
Transducer Excitation Output (standard) |
|||
Output levels Output isolation |
5V@100 mA, 10V@120 mA, 24V@50 mA (jumper selectable) 50V from signal ground |
||
Serial Communications (standard) |
|||
Signal Types Data Rates Output Isolation Serial Protocols Modbus Modes Modbus Compliance Digital Addressing |
RS232 or RS485 (half or full duplex) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Micron ASCII RTU or ASCII Modbus over Serial Line Specification V1.0 (2002) 247 Modbus addresses. Up to 32 devices on an RS485 line w/o a repeater. |
||
Power Input |
|||
Standard power Low power option Power frequency Power isolation Power consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved) 10-48 Vdc or 12-30 Vac DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test 2W typical, 3W with max excitation output |
||
Mechanical |
|||
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw-clamp plugs |
||
Environmental |
|||
Operating Temperature Storage Temperature Relative Humidity Protection Cooling Required |
0°C to 55°C -40°C to 85°C 95% at 40°C, non-condensing NEMA-4X (IP-65) when panel mounted Mount transmitters so that ventilation holes are at top and bottom. Leave 6 mm (1/4") between transmitters, or blow air by means of a fan. |
||