Standard Features
|
DescriptionThe Micron 4-20 mA transmitter for frequency, rate or period accepts two independently scalable input channels from a wide range of pulse sources, such as NPN or PNP proximity switches, contact closures, digital logic, magnetic pickups down to 12 mV, or AC voltages to 250 Vac. Input frequencies can range from 0.005 Hz to 1 MHz. The transmitter output can be selected as 4-20 mA, 0-20 mA or 0-10V, and is isolated to avoid ground loops. Applications include AC line frequency, RPM or speed from proximity switch inputs, and flow from turbine flow meter inputs.
The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control. Standard features of Micron transmitters include:
Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04). |
Analog Input |
|
Types Grounding Channel A Frequency Channel B Frequency Minimum Signal Maximum Signal Noise Filter Contact Debounce Time Base Accuracy |
AC, pulses from NPN, PNP transistors, contact closures, |
Analog Output (standard) |
|
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Update Rate Output Isolation |
4-20 mA and 0-10 Vdc (selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load ) 16 bits (65,536 steps) 0.02% of output span Programmed gate time + 30 ms + 0-2 signal periods 250V rms working, 2.3 kV rms per 1 minute test |
Sensor Excitation Output (standard) |
|
Output levels Output isolation |
5V@100 mA, 10V@120 mA, 24V@50 mA (jumper selectable) 50V from signal ground |
Dual Relay Output (standard) |
|
Relay Type Load rating |
Two solid state relays, SPST, normally open, Form A 130 mA at 140 Vac or 180 Vdc |
Serial Communications (standard) |
|
Signal Types Data Rates Output Isolation Serial Protocols Modbus Modes Modbus Compliance Digital Addressing |
RS232 or RS485 (half or full duplex) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Micron ASCII RTU or ASCII Modbus over Serial Line Specification V1.0 (2002) 247 Modbus addresses. Up to 32 devices on an RS485 line w/o a repeater. |
Power Input |
|
Standard power Low power option Power frequency Power isolation Power consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved) 10-48 Vdc or 12-30 Vac DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test 2W typical, 3W with max excitation output |
Mechanical |
|
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
Environmental |
|
Operating Temperature Storage Temperature Relative Humidity Protection Cooling Required |
0°C to 55°C -40°C to 85°C 95% at 40°C, non-condensing NEMA-4X (IP-65) when panel mounted Mount transmitters so that ventilation holes are at top and bottom. Leave 6 mm (1/4") between transmitters, or blow air by means of a fan. |