Standard Features
|
DescriptionThe Micron 4-20 mA output, process signal input transmitter provides six DC voltage input ranges and four DC current input ranges for use with a wide range of transducers whose output requires zero and span adjustment. All ranges are factory calibrated and jumper selectable. The two most sensitive voltage ranges, 200 mV and 2V, provide a high input impedance of 1 Gohm to minimize the load on the voltage signal. Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control. Digital signal filtering modes are selectable for stable readings in electrically noisy environments. The internal digital readings and analog output can be individually selected to be either unfiltered or filtered. Three analog transmitter settings are jumper selectable: 4-20 mA, 0-20 mA or 0-10V. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy. The output tracks the reading from -99,999 to +99,999 counts that would be transmitted digitally. For DC signals, this reading has a rated accuracy of ±0.01% of full scale input and can be scaled in software. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance. Standard features of Micron transmitters include:
Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04). |
Analog Input |
Range |
Input Ohms |
Voltage |
200.00 mV 2.0000 V 20.000 V 200.00 V 600.0 V |
1 Gohm 1 Gohm 10 Mohm 10 Mohm 10 Mohm |
Current |
2.0000 mA 20.000 mA 200.00 mA 5.000 A |
100 ohms 10 ohms 1 ohm 0.01 ohm |
Input Resolution |
16 bits (65,536 steps) |
|
Analog Output (standard) |
||
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Isolation |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load or higher) 16 bits (65,536 steps) ±0.02% of output span plus conversion accuracy 250V rms working, 2.3 kV rms per 1 minute test |
|
Transducer Excitation Output (standard) |
||
Output levels Output isolation |
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable) 50V from signal ground |
|
Dual Relay Output (standard) |
||
Relay Type Load rating |
Two solid state relays, SPST, normally open, Form A 130 mA at 140 Vac or 180 Vdc |
|
Serial Communications (standard) |
||
Signal Types Data Rates Output Isolation Serial Protocols Modbus Modes Modbus Compliance Digital Addressing |
RS232 (default) or RS485 (half or full duplex) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Micron ASCII RTU or ASCII Modbus over Serial Line Specification V1.0 (2002) 247 Modbus addresses. Up to 32 devices on an RS485 line w/o a repeater. |
|
Power Input |
||
Standard power Low power option Power frequency Power isolation Power consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved) 10-48 Vdc or 12-30 Vac DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test 2W typical, 3W with max excitation output |
|
Mechanical |
||
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw-clamp plugs |
|
Environmental |
||
Operating Temperature Storage Temperature Relative Humidity Protection Cooling Required |
0°C to 55°C -40°C to 85°C 95% at 40°C, non-condensing NEMA-4X (IP-65) when panel mounted Mount transmitters so that ventilation holes are at top and bottom. Leave 6 mm (1/4") between transmitters, or blow air by means of a fan. |
|