DescriptionThe Micron Modbus & serial output, quadrature input transmitter accepts the A & B quadrature encoder signals to provide an analog output that tracks that tracks position, length, angle, or rate. The A & B quadrature signals are 90º out of phase, and their phase relationship determines whether up counts (+) or down counts (-) are produced. One, two or four quadrature transitions may be counted at a maximum combined rate of 250 kHz and be scaled internally to ±999,999. counts. The input circuitry which may be jumpered for either single-ended input signals or for balanced line driver signals. Anti-jitter circuitry eliminates errors produced by vibration of the encoder. In the event of a power failure, the current total may be stored in non-volatile memory and can be used as the starting point for counting when power resumes. Power fail or zero index capabilities are alternate meter setup choices.
Available for Total or Rate
LTM Series serial output transmitters send data via an isolated serial port, which is user configurable for RS232 or RS485 and full or half duplex operation. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Micron ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Micron ASCII protocol allows up to 31 Micron devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Microns. It also allows use of Micron Datalogging Software. Standard features of Micron transmitters include:
Easy Quadrature Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04). |
Quadrature Inputs |
|
Type Transitions Monitored Max Pulse Rate Internal Counts Position Error |
Differential or single-ended quadrature x1, x2 or x4 250 kHz at x1, 125 kHz at x2, 62.5 kHz at x4 -999999 to +999999 No error contributed by transmitter |
Quadrature Position Mode |
|
Zero Adjust Span Adjust |
-999999 to +999999 0 to ±999999 |
Quadrature Rate Mode |
|
Conversion Technique Output Update Rate Gate time Time Before Zero Output Time Base Accuracy Zero Adjust Span Adjust |
Inverse period 30 ms + 0-2 signal periods Selectable 10 ms to 199.99 s Selectable 10 ms to 199.99 s Calibrated to ±2 ppm -999999 to +999999 0 to ±999999 |
Serial Data Output (standard) |
|
Signal levels Data Rates Output Isolation Serial Protocols Devices on RS-485 Line Modbus Addresses Modbus Modes Modbus Compliance |
RS232 or RS485 (half duplex) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Micron ASCII (selectable) 32 max without a repeater. 247 max RTU or ASCII, 2-wire. Modbus over Serial Line Specification V1.0 (2002) |
Transducer Excitation Output (standard) |
|
Output levels Output isolation |
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable) 50V from signal ground |
Dual Relay Output (standard) |
|
Relay Type Load rating |
Two solid state relays, SPST, normally open, Form A 130 mA at 140 Vac or 180 Vdc |
Analog Output (standard) |
|
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Isolation |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load or higher) 16 bits (65,536 steps) 0.02% of output span 250V rms working, 2.3 kV rms per 1 minute test |
Power Input |
|
Standard power Low power option Power frequency Power isolation Power consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved) 10-48 Vdc or 12-30 Vac DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test 2W typical, 3W with max excitation output |
Mechanical |
|
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
Environmental |
|
Operating Temperature Storage Temperature Relative Humidity Protection Cooling Required |
0°C to 55°C -40°C to 85°C 95% at 40°C, non-condensing NEMA-4X (IP-65) when panel mounted Mount transmitters so that ventilation holes are at top and bottom. Leave 6 mm (1/4") between transmitters, or blow air by means of a fan. |