Modbus & Serial Output Transmitter &
Totalizer for 0-1 mA, 4-20 mA or 0-10V


 Scalable to flow rate or total flow from process signals.
DIN Rail mounted, digitally programmable.

4-20 mA Current Transmitters for AC RMS Voltage or Current

 
CE Mark      RoHS Mark
Made in California

Standard Features

  • Selectable Modbus or Micron ASCII protocol
  • Modbus RTU or ASCII modes, 2-wire connection, up to 247 digital addresses
  • Output rate from 0-1 mA, 4-20 mA or 0-10V analog signals
  • Output totalized rate from 0-1 mA, 4-20 mA or 0-10V analog signals
  • Selectable square root extraction for differential pressure flow transducers
  • Output scalable to six transmitted digits:
    - Span adjust from 0 to ±999,999
    - Zero adjust from -999,999 to +999,999
  • Exceptional accuracy: ±0.005% of input span ±1 count
  • Output update rate: 25/sec
  • Peak value capture
  • DIN rail mount package only 22.5 mm thick
  • Detachable screw clamp plug connectors.
  • Easy setup with PC-based Instrument Setup Software
  • 5V, 10V or 24V dc sensor excitation output, isolated
  • Dual solid state relays for alarm or control, isolated
  • 0-10V, 4-20 mA or 0-20 mA analog output, isolated
  • Universal AC power, 85-264 Vac
  • Priced Resonably (basic totalizer transmitter)
    Options:
  • Extended Main Board for custom curve linearization,
    time based on rate (1/rate).
  • Low voltage power, 10-48 Vdc or 12-30 Vac.

Description

The Micron Modbus & serial output totalizing transmitter accepts 0-1 mA, 4-20 mA or 0-10V signals from flow meters and other transducers, such as watt meters, to track rate or totalized rate.

  • With a Standard Main Board, the transmitter output can track rate (such as gallons per minute or watts) or totalized rate (such as gallons or kilowatt hours) whether the transducer output is linear or requires square root extraction (differential pressure flow transducers).
  • With an Extended Main Board, the transmitter can also perform custom curve linearization (provided by a curvilinear spline fit with up to 180 data points), display 1/ rate (such as the time it takes a conveyor to pass through an oven), and perform batch control for repetitive fill operations.  Such applications typically make use of optional dual solid state relays, which are available as options. External reset of totals is provided by a special connector.

Signal Conditioner Board for Laureate Analog Input Flow Rate Meter and Analog Flow TotalizerA signal conditioner board converts the full-scale 0-1 mA, 4-20 mA or 0-10 V analog signal to a frequency of 10 kHz to 110 kHz. This frequency is determined by measuring period over a selected gate time (from 10 ms to 200 s) and taking the inverse of period. At the lowest frequency of 10 kHz and the minimum gate time of 10 ms, the transmitter is capable of 25 updates per second. Scaling is done mathematically. Totals are stored in nonvolatile memory in case of power loss.

LTM Series serial output transmitters send data via an isolated serial port, which is user configurable for RS232 or RS485 and full or half duplex operation. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Micron ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Micron ASCII protocol allows up to 31 Micron devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Microns. It also allows use of Micron Datalogging Software.

Standard features of Micron transmitters include:

  • Serial data output, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or Micron ASCII protocol.
  • Dual solid state relays for control or alarm, isolated. Rated 120 mA at 130 Vac or 170 Vdc.
  • Transducer excitation output, isolated. User selectable 5V@100 mA, 10V@120 mA or 24V@50 mA.
  • Analog transmitter output, 16-bit, user scalable and isolated. User selectable 4-20 mA, 0-20 mA or 0-10V levels.
  • Universal AC power supply for 85-264 Vac.

Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04).


Specifications
Micron Modbus & Serial Output Transmitter &
Totalizer for 0-1 mA, 4-20 mA or 0-10V Inputs

Analog Input
0-1 mA
4-20 mA
0-10 V
Input resistance
Max current or voltage
182 ohms
37 mA
9 ohms
160 mA
1 Mohm
600 V
Input Resolution
Span Tempco
Zero Tempco
Accuracy at 25°C
Read Rate
6 digits
±0.0025% R/°C
±0.0005 FS/°C
±0.005% FS ±1 count
25/sec (typical)
Serial Data Output (standard)
Signal levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance
RS485 (default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Micron ASCII
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002)
Transducer Excitation Output (standard)
Output levels
Output isolation
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable)
50V from signal ground
Dual Relay Output (optional)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc
Analog Output (standard)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
Power Input
Standard power
Low power option
Power frequency
Power isolation
Power consumption
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-30 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output
Mechanical
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw clamp plug connectors
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Protection
Cooling Required
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted
Mount transmitters so that ventilation holes are at top and bottom.
Leave 6 mm (1/4") between transmitters, or blow air by means of a fan.

Pinout
Micron Modbus & Serial Output Transmitter &
Totalizer for 0-1 mA, 4-20 mA or 0-10V Inputs