Standard Features |
|
DescriptionThe Micron Modbus & serial output totalizing transmitter accepts 0-1 mA, 4-20 mA or 0-10V signals from flow meters and other transducers, such as watt meters, to track rate or totalized rate.
LTM Series serial output transmitters send data via an isolated serial port, which is user configurable for RS232 or RS485 and full or half duplex operation. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Micron ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Micron ASCII protocol allows up to 31 Micron devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Microns. It also allows use of Micron Datalogging Software. Standard features of Micron transmitters include:
Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04). |
Analog Input |
0-1 mA |
4-20 mA |
0-10 V |
Input resistance Max current or voltage |
182 ohms 37 mA |
9 ohms 160 mA |
1 Mohm 600 V |
Input Resolution Span Tempco Zero Tempco Accuracy at 25°C Read Rate |
6 digits ±0.0025% R/°C ±0.0005 FS/°C ±0.005% FS ±1 count 25/sec (typical) |
||
Serial Data Output (standard) |
|||
Signal levels Data Rates Output Isolation Serial Protocols Devices on RS-485 Line Modbus Addresses Modbus Modes Modbus Compliance |
RS485 (default) or RS232 (jumper selectable) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Micron ASCII 32 max without a repeater. 247 max RTU or ASCII, 2-wire. Modbus over Serial Line Specification V1.0 (2002) |
||
Transducer Excitation Output (standard) |
|||
Output levels Output isolation |
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable) 50V from signal ground |
||
Dual Relay Output (optional) |
|||
Relay Type Load rating |
Two solid state relays, SPST, normally open, Form A 130 mA at 140 Vac or 180 Vdc |
||
Analog Output (standard) |
|||
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Isolation |
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable) 10V ( 0-500 ohm load ) 2 mA ( 5 kOhm load or higher) 16 bits (65,536 steps) 0.02% of output span plus conversion accuracy 250V rms working, 2.3 kV rms per 1 minute test |
||
Power Input |
|||
Standard power Low power option Power frequency Power isolation Power consumption |
85-264 Vac or 90-300 Vdc (DC operation not UL approved) 10-48 Vdc or 12-30 Vac DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test 2W typical, 3W with max excitation output |
||
Mechanical |
|||
Case Dimensions Case Mounting Electrical Connections |
120 x 101 x 22.5 mm 35 mm rail per DIN EN 50022 Detachable screw clamp plug connectors |
||
Environmental |
|||
Operating Temperature Storage Temperature Relative Humidity Protection Cooling Required |
0°C to 55°C -40°C to 85°C 95% at 40°C, non-condensing NEMA-4X (IP-65) when panel mounted Mount transmitters so that ventilation holes are at top and bottom. Leave 6 mm (1/4") between transmitters, or blow air by means of a fan. |
||