Tools Request Product or Service Information Download Datasheet (acrobat pdf) Print This Page Email this Page to a Friend Magnify Primary Image Buy On-Line Now!  

LTS6 Serial-to-Analog DIN Rail Transmitter

 Converts serial data to a scaled analog signal.

Click on Links for Detailed Product Information

Laurel TS6 Serial-to-Analog DIN Rail Transmitter

 
CE Mark     RoHS Mark
Made in California

 
Standard Features

  • RS-232 or RS-485 serial input
  • Choice of 3 protocols: Modbus RTU, Modbus ASCII, or Micron ASCII
  • Able to retrieve data from long character strings
  • Data rates from 300 to 19,200 bps
  • Isolated 4-20 mA or 0-10V transmitter output, user selectable
  • Output resolution:  0.0015% of span (16 bits)
  • Output accuracy: ±0.02% of span
  • Update rate to 60/sec
  • DIN rail mount package only 22.5 mm (0.89") thick
  • Detachable screw-clamp connectors
  • Easy setup with PC-based Instrument Setup Software
  • Dual solid state relays for alarm or control, isolated
  • Universal AC power, 85-264 Vac
    Options:
  • Low voltage power, 10-48 Vdc or 12-30 Vac

Description

Signal Inputs and Outputs of Laurel TS6 Serial-to-Analog DIN Rail TransmitterThe Micron LTS6 serial input to analog output transmitter accepts RS-232 or RS-485 serial data with the Modbus or Micron ASCII protocol, and converts it to an isolated, scalable 4-20 mA, 0-20 mA or 0-10V analog output signal. The unit fits on a 35 mm DIN rail and is only 22.5 mm (0.89") thick. It is normally powered by AC (85-264 Vac), but can optionally be powered by low voltage AC or DC. All electrical connections are via detachable screw-clamp plugs.

Standard features of the LTS6 include:

  • Analog transmitter output, 16-bit, scalable and isolated. User selectable 4-20 mA, 0-20 mA or 0-10V levels. 16-bit resolution provides an ultra-fine resolution of 0.0015% and accuracy better than 0.02% of output span. Output isolation from signal, power and serial communication grounds is provided by a separate on-board transmitter power supply, thereby eliminating potential problems caused by ground loops. The supply can an drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into 5K ohm (or higher) load for 2 mA compliance.
  • Serial communications, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or Micron ASCII protocol, data rates up to 19200 bps. The RS-232 interface is suitable for short cable runs and point-to-point communications. The RS-485 interface is compliant with the EIA/TIA-485 standard and supports multiple addressable devices on the same data line using the Modbus protocol or Micron ASCII Protocol. Modbus implementation is fully compliant with Modbus over Serial Line Specification V1.0 (2002) in RTU or ASCII, half-duplex or full-duplex operation, with up to 247 digital addresses. The Micron serial-to-analog transmitter is able to retrieve digital data from long character strings. You can specify character positions, start and stop ASCII characters, how many characters to skip, and how many characters to process.
  • Dual solid state relays for control or alarm, isolated. Rated 120 mA at 130 Vac or 170 Vdc.
  • Universal AC power supply for 85-264 Vac.

Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required cable from the transmitters to a PC com port is available from Micron (P/N CBL04).


Specifications
Micron LTS6 Serial Input, Analog Output, DIN Rail Transmitter

Serial Communications (standard)
Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing
RS232 or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Micron ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater.
Analog Output (standard)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Update Rate
Output Isolation
4-20 mA and  0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
16 bits (65,536 steps)
0.02% of output span
Programmed gate time + 30 ms + 0-2 signal periods
250V rms working, 2.3 kV rms per 1 minute test
Dual Relay Output (standard)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc
Power Input
Standard power
Low power option
Power frequency
Power isolation
Power consumption
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-30 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output
Mechanical
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw clamp plug connectors
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Protection
Cooling Required
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted
Mount transmitters so that ventilation holes are at top and bottom.
Leave 6 mm (1/4") between transmitters, or blow air by means of a fan.

 

Pinout
Micron LTS6 Serial Input, Analog Output, DIN Rail Transmitter
Shown with optional dual relay outputs.