Go back  

Tools Request Product or Service Information Download Datasheet (acrobat pdf) Print This Page Email this Page to a Friend Magnify Primary Image Buy On-Line Now!  

LTM SeriesModbus & Serial Output
DIN Rail Transmitters

 DIN Rail mounted, digitally programmable.
Exceptional accuracy at high update rates.

Click on Links for Detailed Product Information

Laurel Electronics Serial ASCII or Modbus Transmitters

 
CE Mark      RoHS Mark
Made in California

   
Standard Features

  • Available for wide choice of analog or pulse signal inputs
  • RS232 or RS485 serial communications, half or full duplex, isolated
  • Modbus RTU, Modbus ASCII or Micron ASCII protocol
  • Output update rate to 60/sec
  • Switching power supply for 85-264 Vac
  • Dual solid state relays for alarm or control
  • 4, 10 or 24 Vdc transducer excitation output, isolated
  • 4-20 mA, 0-20 mA or 0-10V transmitter output, jumper selectable, isolated
  • Easy setup with PC-based Instrument Setup Software
  • DIN rail mount housing only 22.5 mm wide
  • Detachable screw-clamp connector
    Options:
  • Extended main board for custom curve linearization & rate from successive readings
  • Low voltage power 10-48 Vdc or 12-30 Vac

Serial Output Transmitters by Input Signal

Click on the links below for transmitter descriptions and specifications by signal type. Each of the Micron transmitters listed also has a Micron digital panel meter counterpart with the same signal conditioner.

Analog Input Transmitters, Modbus or Micron ASCII I/O:

Pulse Input Transmitters, Modbus or Micron ASCII I/O:
Serial Input (Modbus or Micron ASCII), Analog Output Transmitter:

Description

Removable screw terminal connections of Laurel transmittersMicron LTM Series Modbus & serial output transmitters duplicate the performance and extensive programmable features of their Micron digital panel meter, counter and timer counterparts. They are available for a wide range of analog and pulse input signals types. A related product is Microns. A unique product is Micron's TS6 serial-to-analog converter transmitter, which converts serial data to an isolated analog output.

Micron LTM Series serial output transmitters send data via an isolated serial port, which is user configurable for RS232 or RS485 and full or half duplex operation. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Micron ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Micron ASCII protocol allows up to 31 Micron devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Microns. It also allows use of Micron Datalogging Software.

Easy transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04). The transmitters convert the analog signal into an internal digital reading from -99,999 to +99,999 counts for analog signals and -999,999 to +999,999 counts for pulse signals. Specific readings in counts are then assigned to the desired minimum and maximum analog output. Multiple calibration methods are selectable for use with or without an external calibration reference.

Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion for analog input signals. High read rate is ideal for peak or valley capture and for real-time computer interface and control. Digital signal filtering modes are selectable for stable readings in electrically noisy environments. The internal digital readings and analog output can be individually selected to be either unfiltered or filtered.

Standard features LTM Series transmitters include:

  • Serial data output, isolated. User selectable RS232 or RS485, half or full duplex, Modbus or Micron ASCII protocol.
  • Dual solid state relays for control or alarm, isolated. Rated 120 mA at 130 Vac or 170 Vdc.
  • Transducer excitation output, isolated. User selectable 5V@100 mA, 10V@120 mA or 24V@50 mA.
  • Analog transmitter output, 16-bit, user scalable and isolated. User selectable 4-20 mA, 0-20 mA or 0-10V levels.
  • Universal AC power supply for 85-264 Vac.

Easy Transmitter programming is via Micron's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Micron (P/N CBL04).


General Specifications
Micron LTM Series Modbus & Serial I/O Transmitters

Serial Data Output (standard)
Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing
RS232 or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Micron ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002).
247 Modbus addresses.
Up to 32 devices on RS485 line w/o a repeater
Dual Relay Output (standard)
Relay Type
Load rating
Two solid state relays, SPST, normally open, Form A
130 mA at 140 Vac or 180 Vdc
Analog Output (standard)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
Transducer Excitation Output (standard)
Output Isolation
Selectable Levels
50 Vdc to meter ground
5 Vdc ±5%, 100 mA
10 Vdc ±5%, 120 mA
24 Vdc ±5%, 50 mA
Power Input
Standard power
Low power option
Power frequency
Power isolation
Power consumption
85-264 Vac or 90-300 Vdc (DC operation not UL approved)
10-48 Vdc or 12-30 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2W typical, 3W with max excitation output
Mechanical
Case Dimensions
Case Mounting
Electrical Connections
120 x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw-clamp plugs
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Protection
Cooling Required
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted
Mount transmitters so that ventilation holes are at top and bottom.
Leave 6 mm (1/4") between transmitters, or blow air by means of a fan.
Go back